S-Series : Diffusion Sensor/Transmitter
The RKI S series gas sensor/transmitters are highly reliable and cost effective basic 4-20 mA transmitters for the detection of common gas hazards. The S series transmitters are available for LEL (catalytic), LEL (IR) CH4, LEL (IR) HC, O2, H2S, CO, or CO2 (IR). The electronics are encased inside a potted package to avoid damage from mechanical abuse or corrosion, and this assembly is installed inside an explosion-proof enclosure. All sensors are explosion-proof with flame arrestors and approved for use in hazardous atmospheres. There is also an optional version for oxygen for use in non-hazardous atmospheres.
The only tools required to calibrate the S series are a voltmeter, screwdriver, and cal gas. The zero and calibration functions are performed by adjusting potentiometers on the amplifiers. The amplifier has test jacks for connecting to a voltmeter for calibration purposes, and the sensor response is viewed on the voltmeter as a 100 mV to 500 mV signal. Field calibration can be performed easily and quickly by one person.
The S series transmitters can be used either indoors or outdoors. The flame arrestors utilize a patented coating which make them water repellent, and splash guards are also available for use in very wet environments.
The transmitter operates from 24 VDC (11VDC to 30 VDC), and provides a 4-20mA signal which can be connected to a wide variety of controllers.
ผู้ดูแลระบบ 09/02/2018
The RKI S series gas sensor/transmitters are highly reliable and cost effective basic 4-20 mA transmitters for the detection of common gas hazards. The S series transmitters are available for LEL (catalytic), LEL (IR) CH4, LEL (IR) HC, O2, H2S, CO, or CO2 (IR). The electronics are encased inside a potted package to avoid damage from mechanical abuse or corrosion, and this assembly is installed inside an explosion-proof enclosure. All sensors are explosion-proof with flame arrestors and approved for use in hazardous atmospheres. There is also an optional version for oxygen for use in non-hazardous atmospheres.
The only tools required to calibrate the S series are a voltmeter, screwdriver, and cal gas. The zero and calibration functions are performed by adjusting potentiometers on the amplifiers. The amplifier has test jacks for connecting to a voltmeter for calibration purposes, and the sensor response is viewed on the voltmeter as a 100 mV to 500 mV signal. Field calibration can be performed easily and quickly by one person.
The S series transmitters can be used either indoors or outdoors. The flame arrestors utilize a patented coating which make them water repellent, and splash guards are also available for use in very wet environments.
The transmitter operates from 24 VDC (11VDC to 30 VDC), and provides a 4-20mA signal which can be connected to a wide variety of controllers.
ผู้ดูแลระบบ 09/02/2018
11
M2A : Stand Alone Transmitter
Stand Alone Explosion Proof TransmitterDatasheet• Manual • Spanish Datasheet • Spanish Manual
The RKI M2A™ is a state-of-the-art transmitter that can operate as an independent, stand-alone monitor or as part of an integrated system. The M2A connects with an analog or digital signal to virtually any controller, PLC, or DCS. Setup procedures are simplified with user friendly push buttons and OLED menus. It utilizes a magnetic wand technique for performing non-intrusive calibration. The M2A provides an automatic zero drift correction feature, which results in more stable readings and reduces the need for adjustments due to sensor aging.
The housing of the M2A does not need to be opened for zeroing or calibration, making it unnecessary to declassify the area for routine maintenance. It is designed so that a complete field calibration can be performed by one person. Sensor construction is rated Class I, Div. 1 Groups B, C, D for flammables, CO, H2S, O2, and CO2, and Class I, Div. 2 for all other toxics.
The transmitter provides a 4-20 mA output in addition to a Modbus digital output. It also has two levels of alarms with relays, plus a fail alarm with relay. A digital display of the gas concentration, as well as alarm and status lights, can be viewed through the front window.
The toxic sensors are electrochemical type plug-in sensors, which provide high specificity, fast response, and long life. The plug-in design allows quick replacement in the field with no tools required. Toxic sensors are designed for use in Class I, Div. 2 hazardous locations. Sensors available for NH3, SO2, PH3, AsH3, and HCN.
The M2A represents the latest leading edge technology in sensor / transmitters today.
Features● Operates with or without a controller
● Direct digital readout with OLED display● Available gases include: -LEL, O2, H2S, CO, CO2, and 100% Vol CH4 -Toxic gases include NH3, SO2, HCN, and more● Infrared sensor for combustibles and CO2● 4-20 mA & digital Modbus outputs standard● 2 fully programmable alarm relays & fail relay● Non-intrusive calibration via magnetic wand● Explosion proof construction● Patented water repellent sensor cover● User friendly setup, push buttons & LCD menus● Long-life sensors (2 + years typical).
Applications● Petrochemical plants● Refineries● Water & wastewater treatment plants● Pulp & paper mills● Manufacturing facilities● Automotive● Semiconductor plants● Chemical plants 06/02/2018
Stand Alone Explosion Proof TransmitterDatasheet• Manual • Spanish Datasheet • Spanish Manual
The RKI M2A™ is a state-of-the-art transmitter that can operate as an independent, stand-alone monitor or as part of an integrated system. The M2A connects with an analog or digital signal to virtually any controller, PLC, or DCS. Setup procedures are simplified with user friendly push buttons and OLED menus. It utilizes a magnetic wand technique for performing non-intrusive calibration. The M2A provides an automatic zero drift correction feature, which results in more stable readings and reduces the need for adjustments due to sensor aging.
The housing of the M2A does not need to be opened for zeroing or calibration, making it unnecessary to declassify the area for routine maintenance. It is designed so that a complete field calibration can be performed by one person. Sensor construction is rated Class I, Div. 1 Groups B, C, D for flammables, CO, H2S, O2, and CO2, and Class I, Div. 2 for all other toxics.
The transmitter provides a 4-20 mA output in addition to a Modbus digital output. It also has two levels of alarms with relays, plus a fail alarm with relay. A digital display of the gas concentration, as well as alarm and status lights, can be viewed through the front window.
The toxic sensors are electrochemical type plug-in sensors, which provide high specificity, fast response, and long life. The plug-in design allows quick replacement in the field with no tools required. Toxic sensors are designed for use in Class I, Div. 2 hazardous locations. Sensors available for NH3, SO2, PH3, AsH3, and HCN.
The M2A represents the latest leading edge technology in sensor / transmitters today.
Features● Operates with or without a controller
● Direct digital readout with OLED display● Available gases include: -LEL, O2, H2S, CO, CO2, and 100% Vol CH4 -Toxic gases include NH3, SO2, HCN, and more● Infrared sensor for combustibles and CO2● 4-20 mA & digital Modbus outputs standard● 2 fully programmable alarm relays & fail relay● Non-intrusive calibration via magnetic wand● Explosion proof construction● Patented water repellent sensor cover● User friendly setup, push buttons & LCD menus● Long-life sensors (2 + years typical).
Applications● Petrochemical plants● Refineries● Water & wastewater treatment plants● Pulp & paper mills● Manufacturing facilities● Automotive● Semiconductor plants● Chemical plants 06/02/2018
9
Eagle 2 : PID Portable Gas Monitor
● Special Features● Low flow alarm shuts pump off to avoid damage to instrument.● Hydrophobic filter disc in probe.● Internal hydrophobic filter.● Single gas calibration capability.● Methane elimination feature for environmental applications.● Security Password protected.● Meets EPA Method 21 protocol for fugitive emissions testing (most applications).● Plug and play toxic sensors.● Datalogging available for all configurations.● Transformer gas testing version available.
06/02/2018
● Special Features● Low flow alarm shuts pump off to avoid damage to instrument.● Hydrophobic filter disc in probe.● Internal hydrophobic filter.● Single gas calibration capability.● Methane elimination feature for environmental applications.● Security Password protected.● Meets EPA Method 21 protocol for fugitive emissions testing (most applications).● Plug and play toxic sensors.● Datalogging available for all configurations.● Transformer gas testing version available.
06/02/2018
8
PS-2 : Single Point Stand Alone Monitor
A perfect low cost solution for hydrogen detection in battery rooms, or for LEL or PPM level detection of a variety of flammable or solvent vapors in general industry.
The Model PS 2 is a multipurpose gas monitor utilizing a MOS (metal oxide sensor) for long lasting and low maintenance detection at the LEL or PPM levels of many gases or vapors. The PS 2 has two alarm levels for increasing gas or vapor levels, at the PPM level for detection of many solvent vapors, or for LEL level detection of flammable vapors. Inquire at the factory for your specific requirement. Each alarm level activates a 12 amp relay inside the unit, and terminals are provided for wiring the relay to activate an external alarming device or some other device such as a ventilation fan.
This stand alone unit is housed in a durable plastic enclosure with flanges provided for wall mounting and is designed with easy access wiring hubs on the bottom of the unit. The front of the PS 2 contains three lights; Pilot, Alarm 1, and Alarm 2. An internal audible alarm (85 db) is also built in which activates in a gas alarm condition.
The standard PS 2 is supplied with the gas sensor located on the end of a 30 foot cable (other cable distances are also available). Each unit is powered by 115 VAC standard or 24 VDC as standard (48 VDC versions optional), and the AC version comes complete with a 6' power cord.
PhysicalDimensionsHeight: 6.85” 174 mm
Width 6.48” 165 mm
Depth 3.30” 84 mmEnclosureABS plastic, indoor housingEnvironmentalOperating Temp35°F to 120°F (2°C to 49°C)Relative
Humidity0 - 100% RHSensorsSensorTypesMetal Oxide (MOS / Semiconductor type)Measuring
RangesLEL or PPM levels available for many gases.Sensor
ConnectorSensor is connected to 30’ extension cable wired to terminals inside unit. Cable length can be decreased or increased as needed.
OutputsRelays12 amps for each alarmAudible85 db alarm at 10 cm
VisualAlarm 1: Orange LED
Alarm 2: Red LEDPower115 VAC or 24 VDC
48 VDC (option)
WarrantyOne year materials and workmanship.
Detectable Gases
The PS 2 uses a Metal Oxide Semiconductor (MOS) type sensor for the detection of gases and vapors. This MOS sensor is known for its very long life and truly low maintenance requirements. The PS 2 and its MOS sensor effectively respond to a wide variety of hydrocarbons and other gases or vapors. Alarms can be set for OSHA established TLV levels for many gases or solvent vapors, and at LEL levels for flammable vapor warnings.
Since the PS 2 sensor is a general hydrocarbon sensor, it is not specific for any particular gas. This instrument will perform best if used in an area where the only gas or vapor present, besides fresh air, is the gas or vapor that you wish to detect. If used in an area contaminated with many different gases or vapors, false alarms may occur. Please carefully evaluate the application and the area to ensure that no interfering gases are present.
The PS 2 is an effective solution for solvent vapor monitoring around degreasers or other processes, hydrogen monitoring in battery rooms, natural gas detection in basements around landfills, and many others. Please consult the factory for practical alarm points for your application.
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
Specifications subject to change without notice.Made in the USA 06/02/2018
A perfect low cost solution for hydrogen detection in battery rooms, or for LEL or PPM level detection of a variety of flammable or solvent vapors in general industry.
The Model PS 2 is a multipurpose gas monitor utilizing a MOS (metal oxide sensor) for long lasting and low maintenance detection at the LEL or PPM levels of many gases or vapors. The PS 2 has two alarm levels for increasing gas or vapor levels, at the PPM level for detection of many solvent vapors, or for LEL level detection of flammable vapors. Inquire at the factory for your specific requirement. Each alarm level activates a 12 amp relay inside the unit, and terminals are provided for wiring the relay to activate an external alarming device or some other device such as a ventilation fan.
This stand alone unit is housed in a durable plastic enclosure with flanges provided for wall mounting and is designed with easy access wiring hubs on the bottom of the unit. The front of the PS 2 contains three lights; Pilot, Alarm 1, and Alarm 2. An internal audible alarm (85 db) is also built in which activates in a gas alarm condition.
The standard PS 2 is supplied with the gas sensor located on the end of a 30 foot cable (other cable distances are also available). Each unit is powered by 115 VAC standard or 24 VDC as standard (48 VDC versions optional), and the AC version comes complete with a 6' power cord.
PhysicalDimensionsHeight: 6.85” 174 mm
Width 6.48” 165 mm
Depth 3.30” 84 mmEnclosureABS plastic, indoor housingEnvironmentalOperating Temp35°F to 120°F (2°C to 49°C)Relative
Humidity0 - 100% RHSensorsSensorTypesMetal Oxide (MOS / Semiconductor type)Measuring
RangesLEL or PPM levels available for many gases.Sensor
ConnectorSensor is connected to 30’ extension cable wired to terminals inside unit. Cable length can be decreased or increased as needed.
OutputsRelays12 amps for each alarmAudible85 db alarm at 10 cm
VisualAlarm 1: Orange LED
Alarm 2: Red LEDPower115 VAC or 24 VDC
48 VDC (option)
WarrantyOne year materials and workmanship.
Detectable Gases
The PS 2 uses a Metal Oxide Semiconductor (MOS) type sensor for the detection of gases and vapors. This MOS sensor is known for its very long life and truly low maintenance requirements. The PS 2 and its MOS sensor effectively respond to a wide variety of hydrocarbons and other gases or vapors. Alarms can be set for OSHA established TLV levels for many gases or solvent vapors, and at LEL levels for flammable vapor warnings.
Since the PS 2 sensor is a general hydrocarbon sensor, it is not specific for any particular gas. This instrument will perform best if used in an area where the only gas or vapor present, besides fresh air, is the gas or vapor that you wish to detect. If used in an area contaminated with many different gases or vapors, false alarms may occur. Please carefully evaluate the application and the area to ensure that no interfering gases are present.
The PS 2 is an effective solution for solvent vapor monitoring around degreasers or other processes, hydrogen monitoring in battery rooms, natural gas detection in basements around landfills, and many others. Please consult the factory for practical alarm points for your application.
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
Specifications subject to change without notice.Made in the USA 06/02/2018
7
Direct Connect : Gas Sensors
The RKI direct connect series gas sensors are highly reliable and very cost effective for the detection of common gas hazards. The direct connect series are available for LEL, H2 Specific LEL, Oxygen, H2S, and CO for a variety of RKI's controllers. All sensors are explosion-proof with flame arrestors, and approved (optional non-explosion proof version available for oxygen for use in hazardous atmospheres).The direct connect sensors can be used in two different ways. The sensors can be mounted directly to the controllers as a complete stand alone system, or they can be mounted to explosion proof junction boxes for remote detection.
The direct connect sensors can be used either indoors or outdoors. The flame arrestors for the explosion-proof versions utilize a patented coating which make them water repellent. Also, splash guards are available for use in very wet environments.
All of the direct connect sensors are designed to specifically interface with RKI controllers.
* Specifications subject to change without noticeMade in the USA
06/02/2018
The RKI direct connect series gas sensors are highly reliable and very cost effective for the detection of common gas hazards. The direct connect series are available for LEL, H2 Specific LEL, Oxygen, H2S, and CO for a variety of RKI's controllers. All sensors are explosion-proof with flame arrestors, and approved (optional non-explosion proof version available for oxygen for use in hazardous atmospheres).The direct connect sensors can be used in two different ways. The sensors can be mounted directly to the controllers as a complete stand alone system, or they can be mounted to explosion proof junction boxes for remote detection.
The direct connect sensors can be used either indoors or outdoors. The flame arrestors for the explosion-proof versions utilize a patented coating which make them water repellent. Also, splash guards are available for use in very wet environments.
All of the direct connect sensors are designed to specifically interface with RKI controllers.
* Specifications subject to change without noticeMade in the USA
06/02/2018
6
Beacon 800 : up to 8 Channel Wall Mount Controller
Gas detection should not be complicated. The Beacon™ 800 is gas detection simplified.The Beacon™ 800 is a versatile, low cost fixed system controller for one to eight points of gas detection. It is microprocessor controlled and is capable of accepting up to 8 separate 4-20 mA sensor transmitters which can be either 2 or 3 wire. The Beacon™ 800 can be powered by either 24 VDC, or 85-264 VAC. It is simple to operate and comes complete with a wall mount installation kit.
The 2 large digital displays have backlighting and easily identify both the gas type and the gas concentration for all 8 channels simultaneously. The Beacon™ 800 is housed in a NEMA 4X rated case for a weather tight seal. This case design complies with lock out / tag out standards and can be fully secured. An external reset switch allows alarms to be silenced from outside the controller housing. The bottom mounted wiring hubs allow for easy wiring.
With 3 amp rated relays, the Beacon™ 800 can be wired directly to a variety of devices like alarm horns, buzzers, or lights. This eliminates the need for costly external relays from the controller to devices. RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon™ 800, providing gas monitoring protection for almost any application.
PhysicalDimensionsHeight: 12.5" 318 mmWidth 11.0" 279 mmDepth 6.4" 163 mmEnclosureWall mounting grey polycarbonate with hinged cover.Conduit3/4" NPT conduit hubs, 4 provided for sensors, power and relay wiring.ConnectionWiringScrew type terminal block, 14 gauge max.TerminationEnvironmentalOperating Temp14°F to 122°F (-10°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative0 - 100% RHHumidityEnclosureNEMA-4X enclosure, waterproof, chemical, and weather resistant.RatingInputs4-20 mAAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI sensors are available with4-20 mA signals. Wiring distances up to 8,000 feet.OutputsRelays2 relays per channel 10 amp rating, SPDT isolated contacts.1 set of common relays:2 for gas alarm levels1 for malfunctionRelays fully programmable for:Increasing or decreasing alarmsLatching or self resetNormally energized or normally de-energizedTime delay for alarm on and alarm off24 VDC24 VDC output provided to operate sample drawing adapters.Display2 alphanumeric displays with backlighting. 16 characters per line; 4 lines each. All 8 channels continuously displayed.AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure.Coded Output:pulsing = gas alarmsteady = FailVisual4 visual LED alarms on front cover for alarm indications, pilot, and malfunction.OptionalIndividual 4-20 mA (or 1 - 5 VDC) outputsExpansion CardsHeavy duty relay card (4 each @ 30 amps)Power85-264 VAC or 24 VDC standardBattery backup option availableApprovalsCSA Certified to CSA C22.2 No. 1010 and ANSI/ISA S82.01WarrantyOne year materials and workmanship.
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
06/02/2018
Gas detection should not be complicated. The Beacon™ 800 is gas detection simplified.The Beacon™ 800 is a versatile, low cost fixed system controller for one to eight points of gas detection. It is microprocessor controlled and is capable of accepting up to 8 separate 4-20 mA sensor transmitters which can be either 2 or 3 wire. The Beacon™ 800 can be powered by either 24 VDC, or 85-264 VAC. It is simple to operate and comes complete with a wall mount installation kit.
The 2 large digital displays have backlighting and easily identify both the gas type and the gas concentration for all 8 channels simultaneously. The Beacon™ 800 is housed in a NEMA 4X rated case for a weather tight seal. This case design complies with lock out / tag out standards and can be fully secured. An external reset switch allows alarms to be silenced from outside the controller housing. The bottom mounted wiring hubs allow for easy wiring.
With 3 amp rated relays, the Beacon™ 800 can be wired directly to a variety of devices like alarm horns, buzzers, or lights. This eliminates the need for costly external relays from the controller to devices. RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon™ 800, providing gas monitoring protection for almost any application.
PhysicalDimensionsHeight: 12.5" 318 mmWidth 11.0" 279 mmDepth 6.4" 163 mmEnclosureWall mounting grey polycarbonate with hinged cover.Conduit3/4" NPT conduit hubs, 4 provided for sensors, power and relay wiring.ConnectionWiringScrew type terminal block, 14 gauge max.TerminationEnvironmentalOperating Temp14°F to 122°F (-10°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative0 - 100% RHHumidityEnclosureNEMA-4X enclosure, waterproof, chemical, and weather resistant.RatingInputs4-20 mAAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI sensors are available with4-20 mA signals. Wiring distances up to 8,000 feet.OutputsRelays2 relays per channel 10 amp rating, SPDT isolated contacts.1 set of common relays:2 for gas alarm levels1 for malfunctionRelays fully programmable for:Increasing or decreasing alarmsLatching or self resetNormally energized or normally de-energizedTime delay for alarm on and alarm off24 VDC24 VDC output provided to operate sample drawing adapters.Display2 alphanumeric displays with backlighting. 16 characters per line; 4 lines each. All 8 channels continuously displayed.AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure.Coded Output:pulsing = gas alarmsteady = FailVisual4 visual LED alarms on front cover for alarm indications, pilot, and malfunction.OptionalIndividual 4-20 mA (or 1 - 5 VDC) outputsExpansion CardsHeavy duty relay card (4 each @ 30 amps)Power85-264 VAC or 24 VDC standardBattery backup option availableApprovalsCSA Certified to CSA C22.2 No. 1010 and ANSI/ISA S82.01WarrantyOne year materials and workmanship.
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
06/02/2018
5
Beacon410A
Four Channel Wall Mount Controllerhe Beacon 410A is a highly configurable, microprocessor-based, flexible and easy to use 4 channel gas monitoring controller. It simultaneously displays the gas type, readings, and status for four channels of gas detection. It can monitor any combination of direct connect sensors (LEL, O2, CO2, and toxic gas sensors), as well as any 4-20mA transmitter.
Each channel has up to three fully configurable alarm points. A built-in silenceable audible alarm alerts you to alarm conditions. Each channel also has two dedicated fully configurable relays and there is a bank of common relays as well. The common relays can optionally be configured as additional relays allowing up to 3 alarm relays per channel. Each channel provides a 4-20mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time.
A fully configurable, high visibility strobe is available as an option. The unit can be powered from 115/220 VAC, or an external 24 VDC source. A trickle charging battery backup feature with battery assembly is also available as an option.
All features and functions of the Beacon 410A are controlled by easy to use menus on the OLED display. All features including form-C relay contacts of the Beacon 410A are built into the unit so you never need to purchase or maintain any “add-on” cards or components.
Features
• Simultaneously control up to 4 gas monitoring channels• OLED display of all 4 channels• LEL / O2 / CO2 / toxic direct connect sensors• Accepts any 4-20 mA transmitter, 2 or 3 wire• Up to 3 programmable alarm levels per channel• Up to 3 configurable alarm relays per channel• 4-20 mA analog & Modbus digital output standard• 115 / 220 VAC or 24 VDC operation• Audible alarm with silence feature• RFI / EMI Resistant• Alarm reset switch• Built in trouble alarm with relay• Weather and corrosion resistant NEMA 4X enclosure
PhysicalDimensionsHeight: 12.5”
Width 11”
Depth 6.4”EnclosureNEMA 4X non-metallic for indoor and outdoor locationsConduit
Connection
3/4” NPT conduit hubs, 4 provided, for sensor, power, & relay wiringWiring
Termination
Screw type terminal block, 14 gauge maxPower115 VAC & 220 VAC, or 24 VDC nominal, battery backup option availableControlsDisplay PCB Control Switches:UP/YES push button switch DOWN/NO push button switch ESCAPE push button switch ENTER push button switch External reset switch On/Off toggle switch EnvironmentalOperating Temp-4°F to 122°F (-20°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative
Humidity0 – 95% RH (non-condensing)Enclosure
RatingNEMA-4X enclosure, chemical and weather resistantInputsDirect Wired
SensorsLEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide, and Carbon Dioxide.
Remote amp not required for less than 500 feet4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 8,000 feetSampling MethodsDiffusion and sample draw heads availableOutputsRelaysTwo flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10A contact rating.4-20 mASignal output, 4-20 mA (maximum load impedance 500 ohms), per channelRS-485Modbus format RS-485 serial output of all channel data, including gas reading and alarm status.DisplayFour line OLED displayAudibleBuilt-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = failVisual1. Alarm LEDs (on Display PCB)Alarm 1, yellow Alarm 2, orange Alarm 3, red Fail, yellow 2. Green Pilot LED to indicate AC power connected (on Display PCB)
3. An optional 24 VDC NEMA 4X strobe mounted to top of case.WarrantyOne year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed.Ammonia (NH3)0 – 75.0 ppmArsine (AsH3 )0 – 0.20 ppmBoron Trichloride (BCl3)0 – 15.0 ppmCarbon Dioxide (CO2)0 – 1.0 %Carbon Monoxide (CO)0 – 300 ppmChlorine (Cl2)0 – 3.0 ppmChlorine Dioxide (ClO2)0 – 1.00 ppmChlorine Trifluoride (ClF3)0 – 1.00 ppmCombustibles0 -100% LELDiborane (B2H6)0 – 30.0 ppmFluorine (F2)0 – 6.0 ppmHydrogen (H2)0 – 2000 ppmHydrogen Chloride (HCl)0 – 15.0 ppmHydrogen Fluoride (HF)0 – 9.0 ppmHydrogen Sulfide (H2S)0 -100.0 ppmNitric Oxide (NO)0 -100.0 ppmNitrogen Dioxide (NO2)0 – 15.0 ppmNitrogen Trifluoride (NF3)0 – 30.0 ppmOxygen (O2)0 – 25.0 %Ozone (O3)0 – 1.0 ppmPhosphine (PH3)0 – 1.0 ppmSilane (SiH4)0 – 15.0 ppmSulfur Dioxide (SO2)0 – 30.0 ppmTEOS (Si(OC2H5)4)0 -15/30 ppm 06/02/2018
Four Channel Wall Mount Controllerhe Beacon 410A is a highly configurable, microprocessor-based, flexible and easy to use 4 channel gas monitoring controller. It simultaneously displays the gas type, readings, and status for four channels of gas detection. It can monitor any combination of direct connect sensors (LEL, O2, CO2, and toxic gas sensors), as well as any 4-20mA transmitter.
Each channel has up to three fully configurable alarm points. A built-in silenceable audible alarm alerts you to alarm conditions. Each channel also has two dedicated fully configurable relays and there is a bank of common relays as well. The common relays can optionally be configured as additional relays allowing up to 3 alarm relays per channel. Each channel provides a 4-20mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time.
A fully configurable, high visibility strobe is available as an option. The unit can be powered from 115/220 VAC, or an external 24 VDC source. A trickle charging battery backup feature with battery assembly is also available as an option.
All features and functions of the Beacon 410A are controlled by easy to use menus on the OLED display. All features including form-C relay contacts of the Beacon 410A are built into the unit so you never need to purchase or maintain any “add-on” cards or components.
Features
• Simultaneously control up to 4 gas monitoring channels• OLED display of all 4 channels• LEL / O2 / CO2 / toxic direct connect sensors• Accepts any 4-20 mA transmitter, 2 or 3 wire• Up to 3 programmable alarm levels per channel• Up to 3 configurable alarm relays per channel• 4-20 mA analog & Modbus digital output standard• 115 / 220 VAC or 24 VDC operation• Audible alarm with silence feature• RFI / EMI Resistant• Alarm reset switch• Built in trouble alarm with relay• Weather and corrosion resistant NEMA 4X enclosure
PhysicalDimensionsHeight: 12.5”
Width 11”
Depth 6.4”EnclosureNEMA 4X non-metallic for indoor and outdoor locationsConduit
Connection
3/4” NPT conduit hubs, 4 provided, for sensor, power, & relay wiringWiring
Termination
Screw type terminal block, 14 gauge maxPower115 VAC & 220 VAC, or 24 VDC nominal, battery backup option availableControlsDisplay PCB Control Switches:UP/YES push button switch DOWN/NO push button switch ESCAPE push button switch ENTER push button switch External reset switch On/Off toggle switch EnvironmentalOperating Temp-4°F to 122°F (-20°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative
Humidity0 – 95% RH (non-condensing)Enclosure
RatingNEMA-4X enclosure, chemical and weather resistantInputsDirect Wired
SensorsLEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide, and Carbon Dioxide.
Remote amp not required for less than 500 feet4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 8,000 feetSampling MethodsDiffusion and sample draw heads availableOutputsRelaysTwo flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10A contact rating.4-20 mASignal output, 4-20 mA (maximum load impedance 500 ohms), per channelRS-485Modbus format RS-485 serial output of all channel data, including gas reading and alarm status.DisplayFour line OLED displayAudibleBuilt-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = failVisual1. Alarm LEDs (on Display PCB)Alarm 1, yellow Alarm 2, orange Alarm 3, red Fail, yellow 2. Green Pilot LED to indicate AC power connected (on Display PCB)
3. An optional 24 VDC NEMA 4X strobe mounted to top of case.WarrantyOne year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed.Ammonia (NH3)0 – 75.0 ppmArsine (AsH3 )0 – 0.20 ppmBoron Trichloride (BCl3)0 – 15.0 ppmCarbon Dioxide (CO2)0 – 1.0 %Carbon Monoxide (CO)0 – 300 ppmChlorine (Cl2)0 – 3.0 ppmChlorine Dioxide (ClO2)0 – 1.00 ppmChlorine Trifluoride (ClF3)0 – 1.00 ppmCombustibles0 -100% LELDiborane (B2H6)0 – 30.0 ppmFluorine (F2)0 – 6.0 ppmHydrogen (H2)0 – 2000 ppmHydrogen Chloride (HCl)0 – 15.0 ppmHydrogen Fluoride (HF)0 – 9.0 ppmHydrogen Sulfide (H2S)0 -100.0 ppmNitric Oxide (NO)0 -100.0 ppmNitrogen Dioxide (NO2)0 – 15.0 ppmNitrogen Trifluoride (NF3)0 – 30.0 ppmOxygen (O2)0 – 25.0 %Ozone (O3)0 – 1.0 ppmPhosphine (PH3)0 – 1.0 ppmSilane (SiH4)0 – 15.0 ppmSulfur Dioxide (SO2)0 – 30.0 ppmTEOS (Si(OC2H5)4)0 -15/30 ppm 06/02/2018
4
Beacon 200 : 2 Channel Wall Mount Controller
The Beacon™ 200 is a powerful, low cost fixed system controller for two points of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s most economical two point controller. It is capable of connecting directly to RKI sensors for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beacon™ 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon™ 200 housing, or can be wired remotely from the controller.
The 10 amp rated relays are strong enough to actuate most external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon™ 200’s housing is rated NEMA 4X for corrosion resistance and a weather tight seal, and complies with lock out / tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon™ 200 comes complete with a wall mounting kit for easy installation.
RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon™ 200, providing gas monitoring protection for almost any application.
Physical
Dimensions Height: 10.5” 267 mm Width: 8.5” 216 mm Depth: 6.3” 158 mmEnclosure Wall mounting grey polycarbonate with hinged coverConduit
Connection
3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiringWiring
Termination
Screw type terminal block, 14 gauge maxControls 4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Environmental
Operating Temp 14°F to 122°F (-10°C to 50°C)Storage Temp -4°F to 158°F (-20°C to 70°C)Relative
Humidity 0 - 100% RHEnclosure
Rating NEMA-4X enclosure, waterproof, chemical, and weather resistant
Inputs
Direct Wired Sensors LEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide
Remote amp not required for less than 500 feet4-20 mA Sensors Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feetSampling Methods Diffusion and sample draw heads available
Outputs
Relays 7 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel, plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off4-20 mA Signal output, 4-20 mA (into 1000 ohms impedance maximum), per channel24 VDC 24 VDC (350 mA max) output provided to operate sample drawing adapters or other accessoriesDisplay Alphanumeric display with backlighting. 20 characters per line; 4 lines eachAudible Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = failVisual 4 LED’s on the front cover for alarm status indication, pilot, and malfunctionOptional
Expansion Cards
Individual 4-20 mA (or 1 - 5 VDC) outputs
Heavy duty relay card (4 each @ 30 amps)
Power
115 VAC or 24 VDC standard, Optional 230 VAC. Battery backup option available
Warranty
One year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed
06/02/2018
The Beacon™ 200 is a powerful, low cost fixed system controller for two points of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s most economical two point controller. It is capable of connecting directly to RKI sensors for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beacon™ 200 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon™ 200 housing, or can be wired remotely from the controller.
The 10 amp rated relays are strong enough to actuate most external alarms and horns without using slave relays. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon™ 200’s housing is rated NEMA 4X for corrosion resistance and a weather tight seal, and complies with lock out / tag out standards. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon™ 200 comes complete with a wall mounting kit for easy installation.
RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon™ 200, providing gas monitoring protection for almost any application.
Physical
Dimensions Height: 10.5” 267 mm Width: 8.5” 216 mm Depth: 6.3” 158 mmEnclosure Wall mounting grey polycarbonate with hinged coverConduit
Connection
3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiringWiring
Termination
Screw type terminal block, 14 gauge maxControls 4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Environmental
Operating Temp 14°F to 122°F (-10°C to 50°C)Storage Temp -4°F to 158°F (-20°C to 70°C)Relative
Humidity 0 - 100% RHEnclosure
Rating NEMA-4X enclosure, waterproof, chemical, and weather resistant
Inputs
Direct Wired Sensors LEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide
Remote amp not required for less than 500 feet4-20 mA Sensors Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feetSampling Methods Diffusion and sample draw heads available
Outputs
Relays 7 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel, plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off4-20 mA Signal output, 4-20 mA (into 1000 ohms impedance maximum), per channel24 VDC 24 VDC (350 mA max) output provided to operate sample drawing adapters or other accessoriesDisplay Alphanumeric display with backlighting. 20 characters per line; 4 lines eachAudible Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = failVisual 4 LED’s on the front cover for alarm status indication, pilot, and malfunctionOptional
Expansion Cards
Individual 4-20 mA (or 1 - 5 VDC) outputs
Heavy duty relay card (4 each @ 30 amps)
Power
115 VAC or 24 VDC standard, Optional 230 VAC. Battery backup option available
Warranty
One year materials and workmanship
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed
06/02/2018
3
Beacon 110 : 1 Channel Wall Mount Controller
Gas detection should not be complicated. The Beacon 110 is gas detection simplified.The Beacon 110 is a powerful, low cost fixed system controller for one point of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s best value single gas detection controller. It is capable of accepting RKI sensors directly for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beacon 110 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 110 housing, or can be wired remote from the controller.
The 10 amp rated relays are strong enough to directly power external alarms and horns. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon 110 is also housed in a NEMA 4X rated case for a weather tight seal. This case designcomplies with lock out / tag out standards and can be fully secured. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon 110 ships complete with a wall mounting kit for easy installation.
RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon 110, providing gas monitoring protection for almost any application.
Physical
DimensionsHeight: 8.5" 216 mmWidth 7.0" 178 mmDepth 4.3" 109 mmEnclosureWall mounting grey polycarbonate with hinged cover.Conduit3/4" NPT conduit hubs, 2 provided.Connection1 for sensor wiring 1 for power & relay wiringWiringScrew type terminal block 14 gauge max.TerminationPowerUniversal 115 VAC & 220 VAC, or 24 VDC nominal, battery backup option availableControls3 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Environmental
Operating Temp14°F to 122°F (-20°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative0 - 100% RHHumidityEnclosureNEMA-4X enclosure, waterproof, chemical, and weather resistant.Rating
Inputs
Direct WiredLELSensorsOxygen Carbon Monoxide Hydrogen Sulfide Remote amp not required for less than 500 feet.4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feetSampling MethodsDiffusion and sample draw heads available.
Outputs
Relays3 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarms and 1 trouble relay. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off4-20 mASignal output, 4-20 mA (maximum load impedance 500 ohms), per channel24 VDC24 VDC (400 mA max) output provided to operate sample drawing adapters or other accessoriesDisplay2 x 8 Alphanumeric display with backlighting.AudibleBuilt-in audible alarm, 94 dB, mounted on enclosureCoded output: pulsing = gas alarm, steady = failVisual3 LED’s on the front cover for alarm status indication, and malfunction
WarrantyOne year materials and workmanship
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
Ammonia (NH3)0 - 75.0 ppmArsine (AsH3 )0 - 0.20 ppmBoron Trichloride (BCl3)0 - 15.0 ppmCarbon Dioxide (CO2)0 - 1.0 %Carbon Monoxide (CO)0 - 300 ppmChlorine (Cl2)0 - 3.0 ppmChlorine Dioxide (ClO2)0 - 1.00 ppmChlorine Trifluoride (ClF3)0 - 1.00 ppmCombustibles0 -100% LELDiborane (B2H6)0 - 30.0 ppmFluorine (F2)0 - 6.0 ppmHydrogen (H2)0 - 2000 ppmHydrogen Chloride (HCl)0 - 15.0 ppmHydrogen Fluoride (HF)0 - 9.0 ppmHydrogen Sulfide (H2S)0 -100.0 ppmNitric Oxide (NO)0 -100.0 ppmNitrogen Dioxide (NO2)0 - 15.0 ppmNitrogen Trifluoride (NF3)0 - 30.0 ppmOxygen (O2)0 - 25.0 %Ozone (O3)0 - 1.0 ppmPhosphine (PH3)0 - 1.0 ppmSilane (SiH4)0 - 15.0 ppmSulfur Dioxide (SO2)0 - 30.0 ppmTEOS (Si(OC2H5)4)0 -15/30 ppm
ผู้ดูแลระบบ 31/01/2018
Gas detection should not be complicated. The Beacon 110 is gas detection simplified.The Beacon 110 is a powerful, low cost fixed system controller for one point of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry’s best value single gas detection controller. It is capable of accepting RKI sensors directly for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beacon 110 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 110 housing, or can be wired remote from the controller.
The 10 amp rated relays are strong enough to directly power external alarms and horns. The digital display has backlighting and simultaneous readout of the gas type and concentration.
The Beacon 110 is also housed in a NEMA 4X rated case for a weather tight seal. This case designcomplies with lock out / tag out standards and can be fully secured. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon 110 ships complete with a wall mounting kit for easy installation.
RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon 110, providing gas monitoring protection for almost any application.
Physical
DimensionsHeight: 8.5" 216 mmWidth 7.0" 178 mmDepth 4.3" 109 mmEnclosureWall mounting grey polycarbonate with hinged cover.Conduit3/4" NPT conduit hubs, 2 provided.Connection1 for sensor wiring 1 for power & relay wiringWiringScrew type terminal block 14 gauge max.TerminationPowerUniversal 115 VAC & 220 VAC, or 24 VDC nominal, battery backup option availableControls3 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Environmental
Operating Temp14°F to 122°F (-20°C to 50°C)Storage Temp-4°F to 158°F (-20°C to 70°C)Relative0 - 100% RHHumidityEnclosureNEMA-4X enclosure, waterproof, chemical, and weather resistant.Rating
Inputs
Direct WiredLELSensorsOxygen Carbon Monoxide Hydrogen Sulfide Remote amp not required for less than 500 feet.4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feetSampling MethodsDiffusion and sample draw heads available.
Outputs
Relays3 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarms and 1 trouble relay. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off4-20 mASignal output, 4-20 mA (maximum load impedance 500 ohms), per channel24 VDC24 VDC (400 mA max) output provided to operate sample drawing adapters or other accessoriesDisplay2 x 8 Alphanumeric display with backlighting.AudibleBuilt-in audible alarm, 94 dB, mounted on enclosureCoded output: pulsing = gas alarm, steady = failVisual3 LED’s on the front cover for alarm status indication, and malfunction
WarrantyOne year materials and workmanship
Partial List Of Detectable GasesMany other gases or ranges available. Contact RKI for gases or ranges not listed
Ammonia (NH3)0 - 75.0 ppmArsine (AsH3 )0 - 0.20 ppmBoron Trichloride (BCl3)0 - 15.0 ppmCarbon Dioxide (CO2)0 - 1.0 %Carbon Monoxide (CO)0 - 300 ppmChlorine (Cl2)0 - 3.0 ppmChlorine Dioxide (ClO2)0 - 1.00 ppmChlorine Trifluoride (ClF3)0 - 1.00 ppmCombustibles0 -100% LELDiborane (B2H6)0 - 30.0 ppmFluorine (F2)0 - 6.0 ppmHydrogen (H2)0 - 2000 ppmHydrogen Chloride (HCl)0 - 15.0 ppmHydrogen Fluoride (HF)0 - 9.0 ppmHydrogen Sulfide (H2S)0 -100.0 ppmNitric Oxide (NO)0 -100.0 ppmNitrogen Dioxide (NO2)0 - 15.0 ppmNitrogen Trifluoride (NF3)0 - 30.0 ppmOxygen (O2)0 - 25.0 %Ozone (O3)0 - 1.0 ppmPhosphine (PH3)0 - 1.0 ppmSilane (SiH4)0 - 15.0 ppmSulfur Dioxide (SO2)0 - 30.0 ppmTEOS (Si(OC2H5)4)0 -15/30 ppm
ผู้ดูแลระบบ 31/01/2018
2
Tanker Tester Gas Monitor
RKI is pleased to offer the most versatile portable gas detector specifically for maritime tankers. The EAGLE provides detection combinations never before offered in a portable gas monitor featuring gases like % LEL and volume of hydrocarbons, oxygen, as well as PPM levels of hydrogen sulfide.The EAGLE features include an infrared sensor for combustible gas monitoring in inerted tanks, anddual hydrophobic filters to increase its water resistant performance. For quick response and recovery from distant sampling locations, the EAGLE has a strong internal pump with low flow auto shut off and alarm. The pump can draw samples up to 125 feet even with the dual hydrophobic filters in place. The EAGLE will continuously operate for over 30 hours on alkaline batteries or 18 hours on Ni-Cads. A variety of accessories are also available to help satisfy almost any application such as long sample hoses, datalogging, continuous operation adapters, remote alarms and strobes, extra loud buzzer and alkaline recognition battery charger. The marine versions of the Eagle also include an internal oil mist filter to protect the sampling system.
With its ergonomic design and large glove friendly buttons, the EAGLE offers easy access to controls such as autocalibration, alarm silence, demand zero, peak hold and a wide variety of other features and settings. Each channel has two alarm levels. The two alarm levels are user adjustable and can be latching or self resetting. Rugged, reliable, easy to operate and maintain, the EAGLE is the solution for testing HC vapor levels in inerted tanks. Also, a special version can detect H2S levels up to 1,000 ppm.
EnclosureWeatherproof, chemical resistant, RFI / EMI coated high impact polycarbonate-polyester blend. Can operate in rain or set into 2.5” of water without damage. Ergonomically balanced with rugged top mounted handle.Dimensions10.5” L x 5.9” W x 7” H (26.7 cm x 15 cm x 17.8 cm)Weight5 lbs. (2.27 kg)Detection PrincipleElectrochemical cell, galvanic cell, and infrared.Sensor Life2 years under normal conditions.Sampling MethodPowerful, long-life pump (over 6,000 hours) can draw samples over 125 feet. Flow rate approximately 2.0 SCFH (1 LPM).Display4 x 20 LCD readout. Viewed through window in case top. Displays readings & status of all channels simultaneously. Backlight, automatic for alarms and by demand with adjustable time.Alarms2 alarms per channel. The two alarms are fully adjustable for levels, latching or self reset and silenceable.Alarm MethodBuzzer 85 dB at 30 cm, dual high intensity LED’s, and flashing display.Controls6 External glove friendly push buttons for operation, demand zero, and autocalibration. Buttons also access alarm silence, peak hold, battery status and many other features.Continuous Operating Hours30 Hours minimum using alkaline batteries, or 18 hours using Ni-Cads.Power Source4 Alkaline or Ni-Cad, size D batteries. Charger has alkaline recognition to prevent battery damage if charging is attempted with alkalines.Operating Temp. & Humidity-10°C to 40°C (14°F to 104°F), 0 to 95% RH, non-condensing.Indication AccuracyMaximum variance +/- 5% of full scale.Response Time30 Seconds to 90% using standard 5 ft hose.Safety RatingIntrinsically Safe, Class I, Division 1, Groups A, B, C and D.CSA (C / US) & UL Classified.Standard AccessoriesShoulder strap Alkaline batteries Hydrophobic filter probe 5 foot hose Internal hydrophobic filter Oil mist filter (internal) Manual Training CDOptional AccessoriesDatalogging of up to 4 gases (except 1000 ppm H2S version) Remote alarm Ni-Cad batteries Battery charger, 115 VAC, 220 VAC, or 12 VDC Continuous Operation Adapter, 115 VAC or 12 VDC Extra loud buzzer Extension ProbesWarrantyOne year material and wokmanship Ordering InformationPart NumberDescription72-5354RKHC (100% LEL / 30% Vol. autoranging IR) / O2 / H2S (0-100 ppm)72-5355RKHC (100% LEL / 30% Vol. autoranging IR) / O2 / H2S (0-1,000 ppm)72-5268RKHC (100% LEL / 30% Vol. autoranging IR) / O272-5102RKMOxygen only, 0-25% O272-5121RKHC only (100% LEL / 30% Vol. autoranging IR)
Special Features
• Autoranging display of %LEL & %volume.• Low flow alarm shuts pump off to avoid damage to instrument.• Hydrophobic filter disc in probe.• Internal hydrophobic filter.• Internal oil mist filter• Hoses available up to 125’ long ผู้ดูแลระบบ 30/01/2018
RKI is pleased to offer the most versatile portable gas detector specifically for maritime tankers. The EAGLE provides detection combinations never before offered in a portable gas monitor featuring gases like % LEL and volume of hydrocarbons, oxygen, as well as PPM levels of hydrogen sulfide.The EAGLE features include an infrared sensor for combustible gas monitoring in inerted tanks, anddual hydrophobic filters to increase its water resistant performance. For quick response and recovery from distant sampling locations, the EAGLE has a strong internal pump with low flow auto shut off and alarm. The pump can draw samples up to 125 feet even with the dual hydrophobic filters in place. The EAGLE will continuously operate for over 30 hours on alkaline batteries or 18 hours on Ni-Cads. A variety of accessories are also available to help satisfy almost any application such as long sample hoses, datalogging, continuous operation adapters, remote alarms and strobes, extra loud buzzer and alkaline recognition battery charger. The marine versions of the Eagle also include an internal oil mist filter to protect the sampling system.
With its ergonomic design and large glove friendly buttons, the EAGLE offers easy access to controls such as autocalibration, alarm silence, demand zero, peak hold and a wide variety of other features and settings. Each channel has two alarm levels. The two alarm levels are user adjustable and can be latching or self resetting. Rugged, reliable, easy to operate and maintain, the EAGLE is the solution for testing HC vapor levels in inerted tanks. Also, a special version can detect H2S levels up to 1,000 ppm.
EnclosureWeatherproof, chemical resistant, RFI / EMI coated high impact polycarbonate-polyester blend. Can operate in rain or set into 2.5” of water without damage. Ergonomically balanced with rugged top mounted handle.Dimensions10.5” L x 5.9” W x 7” H (26.7 cm x 15 cm x 17.8 cm)Weight5 lbs. (2.27 kg)Detection PrincipleElectrochemical cell, galvanic cell, and infrared.Sensor Life2 years under normal conditions.Sampling MethodPowerful, long-life pump (over 6,000 hours) can draw samples over 125 feet. Flow rate approximately 2.0 SCFH (1 LPM).Display4 x 20 LCD readout. Viewed through window in case top. Displays readings & status of all channels simultaneously. Backlight, automatic for alarms and by demand with adjustable time.Alarms2 alarms per channel. The two alarms are fully adjustable for levels, latching or self reset and silenceable.Alarm MethodBuzzer 85 dB at 30 cm, dual high intensity LED’s, and flashing display.Controls6 External glove friendly push buttons for operation, demand zero, and autocalibration. Buttons also access alarm silence, peak hold, battery status and many other features.Continuous Operating Hours30 Hours minimum using alkaline batteries, or 18 hours using Ni-Cads.Power Source4 Alkaline or Ni-Cad, size D batteries. Charger has alkaline recognition to prevent battery damage if charging is attempted with alkalines.Operating Temp. & Humidity-10°C to 40°C (14°F to 104°F), 0 to 95% RH, non-condensing.Indication AccuracyMaximum variance +/- 5% of full scale.Response Time30 Seconds to 90% using standard 5 ft hose.Safety RatingIntrinsically Safe, Class I, Division 1, Groups A, B, C and D.CSA (C / US) & UL Classified.Standard AccessoriesShoulder strap Alkaline batteries Hydrophobic filter probe 5 foot hose Internal hydrophobic filter Oil mist filter (internal) Manual Training CDOptional AccessoriesDatalogging of up to 4 gases (except 1000 ppm H2S version) Remote alarm Ni-Cad batteries Battery charger, 115 VAC, 220 VAC, or 12 VDC Continuous Operation Adapter, 115 VAC or 12 VDC Extra loud buzzer Extension ProbesWarrantyOne year material and wokmanship Ordering InformationPart NumberDescription72-5354RKHC (100% LEL / 30% Vol. autoranging IR) / O2 / H2S (0-100 ppm)72-5355RKHC (100% LEL / 30% Vol. autoranging IR) / O2 / H2S (0-1,000 ppm)72-5268RKHC (100% LEL / 30% Vol. autoranging IR) / O272-5102RKMOxygen only, 0-25% O272-5121RKHC only (100% LEL / 30% Vol. autoranging IR)
Special Features
• Autoranging display of %LEL & %volume.• Low flow alarm shuts pump off to avoid damage to instrument.• Hydrophobic filter disc in probe.• Internal hydrophobic filter.• Internal oil mist filter• Hoses available up to 125’ long ผู้ดูแลระบบ 30/01/2018
1
Eagle : Portable Gas Monitor
RKI is proud to produce the most versatile portable gas detector on the market. The EAGLE is a powerful instrument that does more than offer standard confined space protection. The EAGLE also provides detection combinations never before offered in a portable gas monitor featuring the industry’s widest selection of high quality, long life and field proven sensors.
The EAGLE’s ergonomic design offers easy access to controls such as autocalibration, alarm silence, demand zero, peak hold and a wide variety of other features. Each channelhas 2 alarm levels plus TWA and STEL alarms for toxic channels. Alarm levels are adjustable and can be latching or self resetting.
Standard features on the EAGLE are not available on most other competitive units such as PPM/LEL hydrocarbon detection (5 ppm resolution) and a methane elimination switch for environmental applications. For quick response and recovery, the EAGLE has a strong internal pump which can draw samples from over 125 feet. The EAGLE will con-tinuously operate for over 30 hours on alkaline batteries or 18 hours on Ni-Cads. Many accessories such as long hoses, special probes, datalogging, continuous operation adapters, remote alarms and strobes, dilution fittings, inter-nal hydrophobic filter, etc, are available to help satisfy almost any application. Rugged, weather resistant, easy to operate and maintain, the EAGLE is the industry’s answer to portable gas detection in many applications, including land surey.
EnclosureWeather resistant, chemical resistant, RF/EMI coated high impact polycarbonate polyester blend. Can be set in rain or into 2.5 inches of water without damage. Ergonomically balanced with rugged top mounted handle.Dimensions10.5" long x 5.9" x 7" tallWeight5 lbs.Detection PrincipleCatalytic combustion, electrochemical cell, galvanic cell, and infrared.Sensor Life2 years under normal conditions.Sampling MethodPowerful, long-life pump (over 6,000 hours) can draw samples over 125 feet. Flow rate approximately 2.0 SCFH.Display4 x 20 LCD readout with backlighting. Viewed through window in case top. Displays readings & status of all channels simultaneously.Alarms2 alarms per channel plus TWA and STEL alarms. Fully adjustable for levels, latching or self reset and silenceable.Alarm MethodBuzzer 85dB at 30 cm, dual high intensity LED’s, and blinking display.Controls6 external push buttons for operation, demand zero, and autocalibration. Buttons also access LEL/ppm, alarm silence, peak hold, TWA /STEL values, battery status and many other features.Continuous Operating Hours30 hours minimum using alkaline batteries, or 18 hours using Ni-Cads.Power SourceSize D batteries, 4 alkaline or Ni-Cad. Charger has alkaline recognition to prevent battery damage if alkalines are charged.Operating Temp. & Humidity-10°C to 40°C (14°F to 104°F), 0 to 95% RH, non-condensing.Indication AccuracyMaximum variance +/- 5% of full scale.Response Time30 seconds to 90% (for most gases).Safety DesignIntrinsically Safe, Class I, Division 1, Groups A, B, C and D. CSA / NRTL & UL Classified (most versions).Standard AccesoriesShoulder strap, alkaline batteries, hydrophobic probe, and 5 foot hose (for special toxic gas versions, shorter teflon hose used without probe).Optional Accessories• Datalogging of up to 4 gases (No datalogging possible on 5 or 6gas versions or versions with more than 2 toxic sensors)• Remote alarm• Dilution fitting (50/50)• Ni-Cad batteries• Battery charger, 115 VAC, 220 VAC, or 12 VDC• Continuous operation adapter, 115 VAC or 12 VDC• Extra loud buzzer• Extension probes• Internal hydrophobic filter (strongly recommended)WarrantyOne year material and workmanship
Gases & Detectable Ranges
Standard Confined Space GasesHydrocarbons0 - 100% LEL
0 - 50,000 ppmOxygen (O2 )0 - 40% Vol.Carbon Monoxide (CO)0 - 500 ppmHydrogen Sulfide (H2S)0 - 100 ppmSuper Toxics and Other GasesAmmonia (NH3 )0 - 75 ppmArsine (AsH3 )0 - 1 ppm
0 - 200 ppbCarbon Dioxide (CO2 ) (I R Sensor)0 - 5,000 ppm
0 - 10,000 ppm
0 - 5% Vol.
0 - 20% Vol.
0 - 50% Vol.Chlorine (Cl2 )0 - 3 ppmChlorine Dioxide (ClO2 )0 - 1 ppmFluorine (F2 )0 - 5 ppmHydrogen Fluoride (HF)0 - 9 ppmHydrogen Chloride (HCl)0 - 15 ppmHydrogen Cyanide (HCN)0 - 30 ppmMethane (CH4 ) (I R Sensor)0 - 100% LEL
0 - 100% Vol.Nitrogen Dioxide (NO2 )0 - 15 ppmOzone (O3 )0 - 1 ppmPhosphine (PH3 )0 - 1 ppmSilane (SiH4 )0 - 15 ppmSulfur Dioxide (SO2 )0 - 30 ppmThe EAGLE can be provided with up to 6 gas
sensors (4 Toxics maximum). Please specify
gas combination when ordering.
Special Features
• Low Flow alarm shuts pump off to avoid damage to instrument.• Hydrophobic filter disc in probe.• Internal dust filter (or optional internal hydrophobic filter).• Quick autocalibration using 4 in 1 calibration gas standard.• Single gas calibration capability.• Methane elimination switch for environmental applications.• "Adjustment Lockout Switch" for added security.• Confirmation beep (silenceable).• Backlight, automatic for alarms and by demand with adjustable time.• Meets EPA Method 21 protocol for fugitive emissions testing.• Land surveyor (land survey equipment). 30/01/2018
RKI is proud to produce the most versatile portable gas detector on the market. The EAGLE is a powerful instrument that does more than offer standard confined space protection. The EAGLE also provides detection combinations never before offered in a portable gas monitor featuring the industry’s widest selection of high quality, long life and field proven sensors.
The EAGLE’s ergonomic design offers easy access to controls such as autocalibration, alarm silence, demand zero, peak hold and a wide variety of other features. Each channelhas 2 alarm levels plus TWA and STEL alarms for toxic channels. Alarm levels are adjustable and can be latching or self resetting.
Standard features on the EAGLE are not available on most other competitive units such as PPM/LEL hydrocarbon detection (5 ppm resolution) and a methane elimination switch for environmental applications. For quick response and recovery, the EAGLE has a strong internal pump which can draw samples from over 125 feet. The EAGLE will con-tinuously operate for over 30 hours on alkaline batteries or 18 hours on Ni-Cads. Many accessories such as long hoses, special probes, datalogging, continuous operation adapters, remote alarms and strobes, dilution fittings, inter-nal hydrophobic filter, etc, are available to help satisfy almost any application. Rugged, weather resistant, easy to operate and maintain, the EAGLE is the industry’s answer to portable gas detection in many applications, including land surey.
EnclosureWeather resistant, chemical resistant, RF/EMI coated high impact polycarbonate polyester blend. Can be set in rain or into 2.5 inches of water without damage. Ergonomically balanced with rugged top mounted handle.Dimensions10.5" long x 5.9" x 7" tallWeight5 lbs.Detection PrincipleCatalytic combustion, electrochemical cell, galvanic cell, and infrared.Sensor Life2 years under normal conditions.Sampling MethodPowerful, long-life pump (over 6,000 hours) can draw samples over 125 feet. Flow rate approximately 2.0 SCFH.Display4 x 20 LCD readout with backlighting. Viewed through window in case top. Displays readings & status of all channels simultaneously.Alarms2 alarms per channel plus TWA and STEL alarms. Fully adjustable for levels, latching or self reset and silenceable.Alarm MethodBuzzer 85dB at 30 cm, dual high intensity LED’s, and blinking display.Controls6 external push buttons for operation, demand zero, and autocalibration. Buttons also access LEL/ppm, alarm silence, peak hold, TWA /STEL values, battery status and many other features.Continuous Operating Hours30 hours minimum using alkaline batteries, or 18 hours using Ni-Cads.Power SourceSize D batteries, 4 alkaline or Ni-Cad. Charger has alkaline recognition to prevent battery damage if alkalines are charged.Operating Temp. & Humidity-10°C to 40°C (14°F to 104°F), 0 to 95% RH, non-condensing.Indication AccuracyMaximum variance +/- 5% of full scale.Response Time30 seconds to 90% (for most gases).Safety DesignIntrinsically Safe, Class I, Division 1, Groups A, B, C and D. CSA / NRTL & UL Classified (most versions).Standard AccesoriesShoulder strap, alkaline batteries, hydrophobic probe, and 5 foot hose (for special toxic gas versions, shorter teflon hose used without probe).Optional Accessories• Datalogging of up to 4 gases (No datalogging possible on 5 or 6gas versions or versions with more than 2 toxic sensors)• Remote alarm• Dilution fitting (50/50)• Ni-Cad batteries• Battery charger, 115 VAC, 220 VAC, or 12 VDC• Continuous operation adapter, 115 VAC or 12 VDC• Extra loud buzzer• Extension probes• Internal hydrophobic filter (strongly recommended)WarrantyOne year material and workmanship
Gases & Detectable Ranges
Standard Confined Space GasesHydrocarbons0 - 100% LEL
0 - 50,000 ppmOxygen (O2 )0 - 40% Vol.Carbon Monoxide (CO)0 - 500 ppmHydrogen Sulfide (H2S)0 - 100 ppmSuper Toxics and Other GasesAmmonia (NH3 )0 - 75 ppmArsine (AsH3 )0 - 1 ppm
0 - 200 ppbCarbon Dioxide (CO2 ) (I R Sensor)0 - 5,000 ppm
0 - 10,000 ppm
0 - 5% Vol.
0 - 20% Vol.
0 - 50% Vol.Chlorine (Cl2 )0 - 3 ppmChlorine Dioxide (ClO2 )0 - 1 ppmFluorine (F2 )0 - 5 ppmHydrogen Fluoride (HF)0 - 9 ppmHydrogen Chloride (HCl)0 - 15 ppmHydrogen Cyanide (HCN)0 - 30 ppmMethane (CH4 ) (I R Sensor)0 - 100% LEL
0 - 100% Vol.Nitrogen Dioxide (NO2 )0 - 15 ppmOzone (O3 )0 - 1 ppmPhosphine (PH3 )0 - 1 ppmSilane (SiH4 )0 - 15 ppmSulfur Dioxide (SO2 )0 - 30 ppmThe EAGLE can be provided with up to 6 gas
sensors (4 Toxics maximum). Please specify
gas combination when ordering.
Special Features
• Low Flow alarm shuts pump off to avoid damage to instrument.• Hydrophobic filter disc in probe.• Internal dust filter (or optional internal hydrophobic filter).• Quick autocalibration using 4 in 1 calibration gas standard.• Single gas calibration capability.• Methane elimination switch for environmental applications.• "Adjustment Lockout Switch" for added security.• Confirmation beep (silenceable).• Backlight, automatic for alarms and by demand with adjustable time.• Meets EPA Method 21 protocol for fugitive emissions testing.• Land surveyor (land survey equipment). 30/01/2018